Braeburn 140311 3-Zone Control Panel Operation Manual
The Braeburn 140311 is a premier 3-zone control panel designed for single-stage conventional heating/cooling systems. It features LED indicators for operation status, a backlit LCD display, automatic equipment staging, and optional plenum sensor support, ideal for residential and light commercial zoning applications. Below are the key specifications and operation instructions.
Key Specifications
- Type: 3-Zone Control Panel for 1 Heat / 1 Cool Conventional Systems
- Compatibility:
- Single-stage conventional equipment
- Compatible with electric, gas, and oil systems
- Can be used with virtually all conventional low-voltage thermostats
- Not compatible with multi-stage systems beyond specifications or heat pumps
- Power Source:
- Hardwired: 24 VAC, Nominal 60Hz, 18-30 VAC Maximum
- Electrical Rating:
- Panel Power: 6 VA @ 24 VAC
- Current Draw Max: 100 VA @ 24 VAC
- Current Draw Per Zone: 50 VA Max
- Display: 5.5" Backlit LCD showing HEAT CALLS, COOL CALLS, FAN CALLS, PLENUM TEMP
- Operating Conditions:
- Ambient: -22°F to 167°F (-30°C to 75°C)
- Humidity: 5% to 95% RH
- Storage: -40°F to 167°F (-40°C to 75°C)
- Dimensions: 2.1” H x 8” W x 8” D x 10.2” (approximate)
- Features:
- LED indicators for panel status, equipment, thermostats, and dampers
- Electronic self-resetting current limiting
- Optional plenum supply air sensor (Model 149156) for high/low limit protection
- 90-second purge cycle (configurable)
- Automatic equipment staging
- Emergency heat switch (not applicable for conventional)
- Built-in setup menu for configuration
- Thermostat Configuration Options:
- Fan Control: GAS (equipment) or EL (panel)
- Purge Time: 300, 240, 180, 120, 90, 60, 30, 0 seconds
- Supply Air Sensor: YES/NO
- Temperature Scale: °F or °C
- Plenum High Limit: 100-180°F (40-80°C)
- Plenum Low Limit: 30-60°F (0-15°C)
- Short Cycle Protection: 5-0 minutes
- Second Stage Fan: 2 or 3 zones
- Priority Zone: OFF or 1-3
- Opposite Mode Timer: 15-60 minutes
Operation Instructions
Initial Setup
1. Turn Off Power: Always turn off power to the heating/air conditioning system prior to installing or adjusting the Zone Panel.
2. Wire Panel: Wire the entire panel before applying transformer power.
3. Configure System:
- Press SETUP for 3 seconds to enter menu.
- Use SELECT to change values, NEXT to advance, HOLD FOR BACK for 3 seconds to go back, HOLD FOR EXIT for 3 seconds to exit.
- Set options like FAN, PURGE, SA SENS, DEG, PLENUM HI/LO LIMIT, SCP, G2 ZONES, PRIORTY, OP MODE.
Operating the Controller
1. LED Indicators: Panel Power (Green flashing), Equipment (Rh, Rc, Y, G, G2, W), Thermostat (R, Y, W, G per zone), Dampers (Red closed/Green open).
2. Display: Shows HEAT CALLS, COOL CALLS, FAN CALLS, PLENUM TEMP (if sensor enabled).
3. Zone Operation: Dampers open on calls; all open if no calls. Purge at end of call.
4. Staging: Automatic based on configuration.
Note: Use with compatible thermostats and dampers. Plenum sensor protects against high/low temps.
Temperature Display Adjustment
Configure temperature scale (°F/°C) in setup menu under DEG. Changing resets plenum limits. No direct calibration; use separate thermometer for verification if needed.
Troubleshooting
- No Operation: Check power LED, configuration, zone calls.
- No Heat/Cool: Verify thermostat calls, damper LEDs, airflow. Test zones.
- Fan Constant: Check fan control settings, wiring.
- Erratic Operation: Check voltage, fuse, wiring. Reset panel.
- Error Conditions: PLENUM HI (heating off, fan on), PLENUM LO (cooling off, fan on), Plenum Sensor Bad (disable stages/sensor).
- System Checkout: Press TEST for 3 seconds; test heating, cooling, fan, dampers.
- Reset: Press reset once to restart, hold 5 seconds for factory defaults.
Installation Instructions
Warning: Turn off power before installation. For experienced technicians only. Use only with described systems; conform to local codes. Provide disconnect and overload protection.
Remove Old Controller
- Turn off power. Disconnect wiring, note connections. Remove old mounting hardware and controller.
Installing New Controller
- Mount near HVAC equipment in any orientation (wall, stud, truss, plenum), level for appearance. Use base as template, drill holes, secure with screws/anchors.
- Connect thermostats (R, W, Y, G per zone), equipment (Rh, Rc, Y, G, G2, W), dampers (PO/PC per zone), optional plenum sensor, dedicated transformer (R, C).
- Configure via setup menu.
- Push excess wire back.
- Apply power, test system using checkout mode.
Battery Location
- Not applicable; no batteries.
Power Options
Hardwired with dedicated 24 VAC transformer.
Controller Power Method | Description |
Hardwired | Runs on 24 VAC from zoning transformer. |
Caution: Size transformer appropriately. Use slave relay if over max VA. Do not short terminals.
Braeburn Zone Controller Manual© - All Rights Reserved 2025